Chapter 8 Operating Instructions
CLV 490 Bar Code Scanner
8-12
©
SICK AG · Division Auto Ident · Germany · All rights reserved 8 008 796/0000/25-06-2002
Troubleshooting
8.5.3 Malfunctions in Reading mode: result output errors
Check whether the "Device Ready" LED lights up.
If the LED does not light, see
Table 8-5, Page 8-10.
Here: number of bar codes to be read = 1
Malfunction Possible cause Remedy
1. The "Read Result" LED (default setting:
Good Read) does not light up at the end
of the reading pulse.
The "Result 2" switching output
(default setting: Good Read) is not
outputting a pulse
The CLV outputs status ST=2 in the
reading result on the host interface
Read not successful, since there was no
bar code in the reading field during the
reading pulse
Scan line positioned incorrectly
Evaluation range of the scan line is
limited unfavourable (CP values)
Bar code presented at incorrect reading
distance
The presented bar code’s module width
cannot be read by the CLV type being
used
With event-controlled focus control:
wrong focus position in Distance Config-
uration choosen.
With event-controlled focus control:
trigger source parameterized incorrectly.
The bar code is tilted excessively with
respect to the scan line
Synchronize read with presence of an
object in reading field. See
Chapter 8.5.2
Malfunctions in Reading mode: reading
trigger errors, Page 8-11
Align CLV. Is bar code at center of scan
line? Check the reading quality with the
"CLV-Setup" software. Choose P
ERCEN
-
TAGE
E
VALUATION
. See
Chapter 6.5.2 Per-
centage evaluation, Page 6-22
In the "CLV-Setup" program: choose the
R
EADING
C
ONFIGURATION
tab, click the E
DIT
A
UTOFOCUS
respectively D
ISTANCE
C
ONFI
-
GURATION
/A
SSIGMENT
TABLE
button. Are the
min. and max. code position values cor-
rect? Check with S
HOW
CP-
LIMITS
. See
Chapter 6.5.5 Show CP-limits,
Page 6-26
Check whether reading distance of bar
code is in the specified reading range?
Present a bar code with an acceptable
module width. See
Chapter 9 Technical
data, Page 9-1
In the "CLV-Setup" program: choose the
R
EADING
C
ONFIGURATION
tab, click the D
I
-
STANCE
C
ONFIGURATION
/A
SSIGNMENT
T
ABLE
button. Does the focus position match
the distance of the object?
In the "CLV-Setup" program: choose the
R
EADING
C
ONFIGURATION
tab, in the
F
OCUS
T
RIGGER
section.
a) Trigger source "Switching input":
Check functional assignment of IN 3 and
IN 4 and connection of the sensors. See
Fig. 5-5, Page 5-17
b) Trigger source: "Serial interface":
Check the data connection to the host.
Use the "CLV-Setup" program to check
the host command strings: choose A
UXI
-
LIARY
I
NTERFACE
tab. Choose M
ONITOR
H
OST
I
NTERFACE
function. See
Chapter 6.5.8 Monitor Host Interface,
Page 6-29
. Download temporarily to
CLV!
c)Trigger source: Timer:
Check switchover time
In the "CLV-Setup" program: choose the
C
ODE
C
ONFIGURATION
tab , D
ECODER
sect io n :
choose SMART decoder.
Download all changes to CLV!
Table 8-7: Troubleshooting: result output errors in Reading mode